Where Do 30 Tonnes of Rainwater Go After a Downpour?

Where Do 30 Tonnes of Rainwater Go After a Downpour?

Where Do 30 Tonnes of Rainwater Go After a Downpour?

Imagine 30 millimetres of rain falling on a 1,000 m² warehouse roof. That adds up to around 30 cubic metres of water, or 30 tonnes. If the same amount falls in 15 minutes instead of an hour, the average rate at which water reaches the roof is four times higher. During heavy rainfall, what matters is how quickly the roof can drain and where the water goes once it leaves the building.

At a logistics facility, rainwater collected during a downpour can be used to irrigate the grounds a few days later. That takes planning all the way from the roof outlet to the storage tank and the point of use. EBITT e-WAC brings these stages together through siphonic roof drainage, rainwater storage, filtration and reuse.

What is siphonic roof drainage and how does it work?

Siphonic roof drainage is designed to carry rainwater through pipes that run completely full once the flow reaches the required level. Anti-vortex roof outlets collect water while limiting the amount of air entering the pipework. As the flow increases, water pushes the remaining air out of the system. Once the pipes are full, the difference in elevation between the roof and the discharge point drives the flow, creating below-atmospheric pressure in parts of the pipework.

In conventional gravity roof drainage, water and air share the pipe cross-section. Under design conditions, a siphonic system uses the full cross-section to carry water. Depending on the project, this can deliver the required drainage capacity with smaller pipe diameters and fewer downpipes. Connecting multiple outlets to a single horizontal collector also gives designers more flexibility to coordinate pipe routes with the building structure and other services.

These advantages are especially relevant for buildings with large roofs, including factories, warehouses, shopping centres, airports, stadiums and other commercial facilities.

What are the components of the EBITT e-WAC siphonic roof drainage system?

Component Function
Anti-vortex roof outlet Collects rainwater from the roof and limits air entry into the pipework.
Branch pipe Carries water from each outlet to the main collection line.
Horizontal collector Combines flow from multiple branches and directs it to the downpipe.
HDPE pipes and electrofusion couplings Form the corrosion-resistant drainage network. Electrofusion couplings create watertight joints between pipes.
Pipe clamps, supports and hangers Secure the suspended pipework to the building structure. The support arrangement accounts for the weight of water-filled pipes and thermal movement.
Vertical downpipe Carries water from the horizontal collector to the discharge level.
Discharge connection Connects the downpipe to the site drainage network or the line leading to storage through a suitable transition.

The suspended HDPE pipework offers corrosion resistance and requires little maintenance. Accessible roof outlets make routine inspection and cleaning easier.

Siphonic roof outlet models and flow rates

Roof outlet model Outlet diameter Catalogue flow range
EB-BC-75 DN75 6–24 L/s
EB-BC-90 DN90 24–42 L/s
EB-BC-125 DN125 42–70 L/s

The flow ranges apply to the individual outlet models. The required flow at each outlet is determined by the roof area it serves and the hydraulic conditions of the pipe network.

How is a siphonic roof drainage system sized?

Hydraulic design starts with the effective roof catchment area and the design rainfall intensity for the site. Rainfall depth gives the total volume of water. Sizing outlets and pipes also requires knowing how quickly that volume reaches the roof. The calculation accounts for the roof layout, outlet positions, pipe lengths, fittings, elevation differences and discharge conditions.

Siphonic drainage design software uses the hydraulic data for the selected outlets to check branch flow rates, pipe diameters, flow velocities, pressures and the hydraulic balance between branches. If an outlet model, pipe diameter or route changes during installation, the hydraulic calculation should be revisited to assess the effect on the entire network.

The design should also consider emergency overflow or secondary roof drainage for rainfall exceeding the primary system’s design conditions. The roof overflow provides a separate route for water accumulating on the roof. The storage tank overflow carries excess water away once the tank reaches capacity.

How does rainwater get from the roof to the storage tank?

Once it leaves the roof, rainwater travels through enclosed pipework to the storage area. The example layout in the EBITT e-WAC catalogue shows how the water can be diverted, pre-filtered and settled before it enters storage.

  1. Flow diversion. A safety diversion chamber directs water into the route designated for the project.
  2. Pre-filtration and sedimentation. A filter chamber intercepts pollutants, while a sedimentation chamber for the initial runoff helps keep settleable particles out of storage.
  3. Storage. A distribution pipe carries rainwater to the storage modules. Depending on site conditions, a modular underground reservoir or a polyethylene tank can be used.
  4. Filtration and reuse. The example layout includes a control panel and a fully automatic filter in a control cabinet. A reuse pump supplies the distribution line. The layout also shows a discharge pump and line, a manual butterfly valve, a valve chamber and a backwash line. Filtration and treatment are selected according to the water quality required at the point of use.
  5. Overflow and discharge. When storage reaches capacity, excess water is routed to the stormwater network or another approved discharge point. Where soil and groundwater conditions allow, an infiltration chamber or soakaway can return excess water to the ground in a controlled manner.

How do you choose a rainwater storage tank?

Tank capacity depends on the amount of water the roof can collect, seasonal rainfall patterns, demand for reuse and the space available on site. A tank can hold back part of the runoff when it has spare capacity at the start of a storm. Planning where excess water will go once the tank is full is part of sizing the system.

Feature Modular underground storage Polyethylene storage tank
Material Reinforced polypropylene (PP) Rotationally moulded polyethylene (PE)
Configuration Interlocking cells installed underground Horizontal and vertical models for above-ground or underground installation, depending on the model
Capacity Configured for each project, with up to 1,000 m³ stated in the technical table A range of tank sizes and capacities
Durability and maintenance High structural strength, no additional corrosion protection required for the PP structure, long service life and low maintenance UV and corrosion resistance, low maintenance and an optional food-contact-grade material
Applications Car parks, roads, sports fields, parks, landscaped areas, commercial buildings and industrial facilities Houses, apartment buildings, schools, hotels, farms and commercial buildings

Modular underground storage uses lightweight cells that are easy to assemble. Additional cells can increase capacity where site conditions allow. A high void ratio means more of the excavated volume is available for water storage. The foundation layer provides structural support, geotextile separates the storage structure from the surrounding soil, and compacted backfill distributes surface loads. Once loading and burial conditions are verified for the project, the surface above the reservoir can be used for roads, parking or landscaping.

Polyethylene tanks are shown in the catalogue with an inlet, overflow outlet, vent, inspection cover and base support. In underground installations, the tank bedding and backfill are specified according to the model and site loads. The food-contact-grade option refers to the tank material. Whether harvested rainwater is suitable for drinking depends on treatment and verification of water quality.

What can harvested rainwater be used for?

With appropriate filtration and any treatment required for the intended use, harvested rainwater can supply garden and landscape irrigation, toilet flushing, vehicle washing, agricultural irrigation and other non-potable applications. The catalogue also illustrates laundry and pool top-up as possible uses where the applicable water quality and hygiene requirements are met.

For example, a logistics facility can store roof runoff during a downpour and use it to irrigate landscaped areas in the days that follow. This can reduce the amount of mains water used for irrigation. The savings depend on how much rainwater the facility can store and how much water it uses over time.

Frequently asked questions

Does siphonic roof drainage run full during every rainfall event?

During light rain, the pipes may run partially full. Full-bore flow begins when the rainfall generates enough runoff to fill the pipework and expel the air.

Does siphonic roof drainage need a pump?

Siphonic flow is driven by the difference in elevation between the roof and the discharge point. A separate pump can be used downstream to deliver stored rainwater to the points of use.

What happens when a rainwater storage tank is full?

Excess water leaves through a dedicated overflow line sized for the project and is routed to the stormwater network or an approved discharge point. Controlled infiltration may also be an option where soil permeability, groundwater levels and other site conditions allow.

Plan your rainwater system with EBITT

If you are designing roof drainage for a new facility or looking to reuse rainwater at an existing building, share your project location, roof plan and intended uses for the collected water. The EBITT technical team can review the siphonic drainage design, roof outlet selection, storage capacity and reuse network for your project.